FLOWSIC100 Operating Instructions
Gas Velocity Monitor
Assembly and Installation
70
©
SICK MAIHAK GmbH · Germany · All rights reserved
88012513/03-2008
Prerequisite for Use of the Control Unit MCU-P (for FLSE100-MAC and HAC)
Additionally to the general requirements the following is prerequisites apply:
The purge-air unit must be mounted at a location with clean air. The intake temperature
must match the values specified in the technical data (see Section 2.6). If necessary, lay
an intake hose at a location where the conditions are more favorable.
The purge-air hoses to both sender/receiver units should be as short as possible. They
must be of equal length (max. hose length in each case 10 m).
The purge-air hoses should be laid in such a way that water cannot collect. If necessary,
provide a small opening at the lowest point on the hose (with a screwdriver, for example).
If the control unit must be mounted at more than 10 m distance, the following equipment
is additionally needed:
a separate fan unit (dimensions and mounting dimensions as MCU-P; Part No
7040289)
two purge-air hoses 40 (Part No 5304683, bulk stock)
two adapters 40-25 (Part No 7047019)
3.2.3 Installing the Connection Box
For assembly at stone /
concrete ducts suitable
mounting set are avail-
able.
This modules should be mounted on a level base plate (secure with 2 bolts M4x20).
Fig. 3.14: Mounting dimensions for connection box
Clearance for cables
> 150 > 15080
52
M4
113