123 / 244 
Siemens  Standard application AHU  CE1P3977en_02 
Building Technologies  Communication  01.02.2010 
Parameter  Range  Function 
Software version    Module software version. 
Device ID.    Module internal device ID. 
Modules    Module type. 
Use default  −  Passive 
−  Active 
Reset parameterization to default values. 
Reset required !! 
−   
−  Execute 
As a matter of principle, the controller must be 
set after changing the settings to assume the 
data. 
 
Main Index > System overview > Communication > Comm module overview > 
Module[x] Modbus > Settings channel 0 / 1 
 
Main Index > System overview > Communication > Modbus > Module[x] 
Modbus 
 
Parameter  Range  Function 
Enable.  −  Passive 
−  Active 
Modbus channel 1 only: Enable Modbus channel 
1. 
Slave address    Set address for the Modbus connection on the 
bus. 
Baud rate 
 
 
Baud rate (Forts.) 
−  2400 
−  4800 
−  9600 
−  19200 
−  38400 
Transmission rate settings per the Modbus. 
Stop bits   
−  One 
−  Two 
Displays number of stop bits: 
−  One stop bit. 
−  Two stop bits. 
Parity  −  None 
−  Even 
−  Odd 
Parity setting. 
Response timeout  0…3600 [sec]  Settings access time for master. 
The master must undertake read access within 
this period, otherwise an alarm is triggered (this 
function is not yet fully implemented). 
Termination   
 
−  Passive 
−  Active 
A RS485 topology must always be ended using 
wave resistors. 
−  Terminating resistor disabled. 
−  Terminating resistor enabled. 
Reset required !! 
−   
−  Execute 
As a matter of principle, the controller must be 
set after changing the settings to assume the 
data. 
 
 
Parameterize Modbus 
channels 
Basis Document Siemens Climatix Control System
BDCX.100820.01GB
Page 123