Siemens Standard application AHU CE1P3977en_02
Building Technologies Functions 01.02.2010
Master Index > Unit > Temp control > Heat recovery > Frost
Parameter Range Function
Controller 0...100 [%] Present value for the frost controlled. Go to con-
troller settings page.
Setpoint -64...64 [°C] For temperature frost protection only!
For one setpoint: Present setpoint for the frost
controller.
Fan stage 1 stpt 0...5000 [Pa] For air-side frost protection only!
Setpoint for the controller at fan stage 1.
Fan stage 2/3 stpt 0...5000 [Pa] For air-side frost protection only!
Setpoint for the controller at fan stage 2 and 3.
5.8 Heating / Heating 2
5.8.1 General
Heating / heating 2 is enabled and preconfigured in configuration 1, configuration 2
and configuration I/Os.
Main Index > Configuration > Configuration 1
Parameter Range Function
Heating /
Heating 2
No
Yes
Yes+Preheat
No (additional) heating register.
(Additional) heating register without preheating.
(Additional) heating register with preheating.
Main Index > Configuration > Configuration 2
Parameter Range Function
Htg frost protect /
Heating 2 frost
No
sensor
Sensor2Spv
Detector
Snsr+Dtctr
2Spv+Dtctr
No frost protection.
Frost protection using a sensor.
Frost protection using a sensor and 2 setpoints.
Frost protection using a detector.
Frost protection using a sensor and detector.
Frost protection using a sensor, 2 setpoints and
detector.
Heating pump /
Heating 2 pump
No
Yes
Yes+Kick
No heating register pump.
Heating register pump without pump kick.
Heating register pump with pump kick.
Htg pump alarm /
Heating 2 pump alm
No
Alarm
Fdbk
Both
Pump without alarm or feedback.
Pump with alarm.
Pump with feedback.
Pump with alarm and feedback.
Heating 2 control StandAlone
InSequence
Not integrated in sequence.
Integrated in sequence.
The hot ware registers can be operated with pump (pump kick, alarm, feedback) or
without pump. Frost detection and controlled frost protection is integrated. The ad-
ditional heating register can be operated as a separate register with its own set-
point. The heating register is forced off if:
Night unoccupied (temperaturstart) cool
Summer night cooling
Combicoil at summer (only heating, not heating2)
A maximum of one of the two additional registers Heating 2 or El heating 2 can be
integrated into the temperature control sequence.
Parameter
Prerequisite
Enable heating group
Configuration
Function
Note
Basis Document Siemens Climatix Control System
BDCX.100820.01GB
Page 73

Table of Contents

Other manuals for Siemens Climatix Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Climatix Series and is the answer not in the manual?

Siemens Climatix Series Specifications

General IconGeneral
ApplicationHVAC control
Communication ProtocolsBACnet, Modbus, KNX
InputsAnalog and digital inputs
OutputsAnalog and digital outputs
User Interfaceweb interface
Power Supply24 V AC
Protection ClassIP20
MountingDIN rail mounting

Related product manuals