59 / 244 
Siemens  Standard application AHU  CE1P3977en_02 
Building Technologies  Functions  01.02.2010 
5.5  Temperature control 
5.5.1  General 
 
Displays only the functions enabled in configuration 1 or configuration 2. All other 
functions are hidden. General there is a mix of use of exhaust and return air 
sensor! 
Main Index > Unit > Temp control 
Parameter  Function 
Act controlled tmp  Present temperature used for control. Eight supply air, room or return tempera-
ture depending on the setting and control type. 
Tmp setpoints  Go to setpoint page with all setpoints affected by temperature control, e.g. com-
fort, economy, cascade min max, deviation alarm, summer-winter compensation. 
Cascade controller  Displays heating and cooling setpoint. Go to cascade controller page with de-
tailed settings. 
Min/max ctrlr sply  Go to page for min/max ctlr sply to parameterize the minimum and maximum limit 
controller. You can use the existing supply air sensor to limit the minimum or 
maximum allowable supply air temperature if purely room or return air control is 
active. 
Hrec damper  Present value of the mixed aid damper control. Go to parameter page for mixed 
air damper control. 
Heat recovery  Present value for heat recovery control. Go to parameter page for heat recovery 
control. 
Heating  Present value for heating register control. Go to parameter page for heating regis-
ter control. 
Electrical heating  Present value for electrical heating register control. Go to parameter page for 
electric heating register control. 
Cooling  Present value for cooling register control. Go to parameter page for cooling regis-
ter control. 
Heating 2  Present value for heating register control for an additional register. Go to parame-
ter page for heating register control. 
El Heating 2  Present value for electric heating register control for an additional register. 
Go to parameter page for electric heating register control. 
Cooling 2  Present value for cooling register control for an additional register. Go to parame-
ter page for cooling register control. 
Fan heating  Present value of the fan heating sequence. Go to parameter page for fan heating 
sequence. 
Fan cooling  Present value of the fan cooling sequence. Go to parameter page for fan cooling 
sequence. 
Fan compensation  Present value of the fan temperature compensation. Go to parameter page for 
fan temperature compensation. 
 
 
Prerequisite 
Parameterization 
Basis Document Siemens Climatix Control System
BDCX.100820.01GB
Page 59