5.5.2  Temperature setpoints 
 
Displays only the functions enabled in configuration 1 or configuration 2. All other 
functions are hidden. 
Main Index > Unit > Temp control > Tmp setpoints 
Parameter  Range  Function 
Act controlled tmp  ---  Present temperature used for control. 
Eight supply air, room or return temperature depending on 
the setting and control type. 
Act cooling stpt  ---  Present calculated room or supply air setpoint for cooling. 
Act heating stpt  ---  Present calculated room or supply air setpoint for heating. 
Act sply clg stpt  ---  Present calculated supply air setpoint in cooling for a cas-
cade control.  
Act sply htg stpt  ---  Present calculated supply air setpoint in heating for a cas-
cade control. 
External setpoint  ---  Present external setpoint or setpoint compensation. 
Sply air comp  -10.0…10.0 [°C] 
 
Setpoint compensation for winter operation for: 
Tmp control mode = RmSplyC Su (Room supply air cas-
cade control in summer, pure supply air control in winter). 
or 
Tmp control mode = RtSplyC Su (return supply air cas-
cade control in summer, pure supply air control in winter). 
The room setpoint for cascade control, active in the sum-
mer, are active (summer - winter changeover). 
During winter, these room setpoints must be adapted to 
the supply air control. 
Comfort setpoint  0…99 [°C]  Comfort based setpoint. Only available when Tmp stpt 
selection = +/-Half degree Celsius. 
Comfort cooling  0…99 [°C]  Comfort cooling setpoint. Only available when Tmp stpt 
selection = Htg/Clg or Clg-degrees Celsius. 
Comfort heating  0…99 [°C]  Comfort heating setpoint. Only available when Tmp stpt 
selection = Htg/Clg or Htg-degrees Celsius. 
Comfort deadzone  0…20 [°C]  Comfort dead zone. Only available when Tmp stpt selec-
tion = Clg-degrees Celsius or Htg+degrees Celsius or  +/-
Half degree Celsius. 
Economy setpoint  0…99 [°C]  Economy base setpoint. Only available when Tmp stpt 
selection = Spv+Halfdegree Celsius. 
Economy cooling  0…99 [°C]  Economy setpoint for cooling. Only available when Tmp 
stpt selection = Htg/Clg or Clg-degrees Celsius. 
Economy heating  0…99 [°C]  Economy setpoint for heating. Only available when Tmp 
stpt selection = Htg/Clg or Htg-degrees Celsius. 
Economy deadzone  0…20 [°C]  Economy dead zone. Only available when Tmp stpt selec-
tion = Clg-degrees Celsius or Htg+degrees Celsius or  +/-
Half degree Celsius. 
Extra Seq setpoint  0…99 [°C]  Setpoint for Heating 2, El Heating 2, Cooling 2 if config-
ured as stand alone. 
Supply tmp min stpt  15.0… Supply tmp 
max stpt [°C] 
Lower allowable supply air temperature for pure room or 
return air control with additional available supply air sen-
sor. Limited control of the cooling setpoint occurs if the 
supply air temperature < Supply tmp min. The heating reg-
ister is started if this is not enough. 
Supply tmp max stpt  Supply tmp min stpt 
… 50.0 [°C] 
Highest allowable supply air temperature for pure room or 
return air control with additional available supply air sen-