90 / 244   
Siemens  Standard application AHU  CE1P3977en_02 
Building Technologies  Functions  01.02.2010 
Main Index > Unit > Humidity control > Fan compensation 
Parameter  Range  Function 
Controller  0…100 [%]  Present value for the controller. Go to controller set-
tings page. 
Setpoint  0…100 [%]  Controller setpoint relating to the room humidity. 
Function  –  Increase 
–  Decrease 
–  Increase the fan setpoint. 
–  Reduce the fan setpoint. 
 
–  Room humidity setpoint: 50 %rH. 
–  Present room humidity: 40 % rH.  
---> Controller output > 0 % (e.g. 50 %).  
 
Switch function: Increase 
The controller output increases the fan setpoint relating to the maximum allowable 
fan compensation (See as well Fan compensation). 
–  Setpoint supply air pressure: 80 Pa (maximum possible setpoint = Setpoint of 
the maximum enabled stage + Max Force, e.g. = 120 Pa). 
–  Maximum allowable fan compensation (100 % compensation): 40 %. 
–  Controller output: 50 %. 
---> New setpoint = 80 Pa + (40 Pa * 50 %) = 100 Pa. 
Switch function: Decrease 
The controller output reduces the fan setpoint relating to the maximum allowable 
fan compensation (See as well Fan compensation). 
–  Setpoint supply air pressure: 80 Pa (maximum possible setpoint = Setpoint of 
the maximum enabled stage + Max Force, e.g. = 120 Pa). 
–  Maximum allowable fan compensation (100 % compensation): 40 Pa. 
–  Controller output: 50 %. 
---> New setpoint = 80 Pa – (40 Pa * 50 %) = 60 Pa. 
 
 
5.12  Air quality control 
 
Main Index > Configuration > Configuration 2 > Fan comp air qual = Yes 
und/oder 
Main Index > Configuration > Configuration 1 > Hrec comp air qual = Yes 
Fans (see fan compensation) and/or mixed air dampers are influenced based on 
air quality. The fresh air volume is increased when CO
2 
content is too high (fan 
speed increases; recirculation flow is reduced). The fresh air volume is increased 
when CO
 
content is too high (fan speed decreases; recirculation flow is increased). 
Main Index > Unit > Air quality control 
Parameter  Range  Function 
Controller  0…100 [%]  Present value for the controller. Go to controller set-
tings page. 
Function   
 
–  Normal 
–  Inverted 
The control direction of the controller must be se-
lected depending on demand: 
Normal for CO
2.
 
Inverted for CO. 
Setpoint  0…3000 [ppm]  Air quality control setpoint. 
 
Parameterization 
Example 
Prerequisite 
Function 
Parameter 
Basis Document Siemens Climatix Control System
BDCX.100820.01GB
Page 90