189 / 244
Siemens Standard application AHU CE1P3977en_02
Building Technologies HMI 01.02.2010
17.10 Global functions
17.10.1 General
Main Index > Unit > Global Function
Parameter Function Value range Unit Standard R S Link
Su/Wi calculation Status of Summer Winter compensation Winter
Summer
X
Manual mode Status from the Plant if anything is in
Manual Mode
Manual
Auto
X
Enable manual alarm Enable the Alarm for Manual Mode No
Yes
No 6 Section:
5.1.1
Enable comm test Enable the comminication Test No
Yes
No 6
Communication test Staus from the communication Test Off
On
Off
17.10.2 Su-Wi compensation
Main Index > Unit > Global Function > Su-Wi compensation
Parameter Function Value range Unit Standard R S Link
State State of Summer Winter Compensation Winter
Summer
Su/Wi input Status of the Heardware input Winter
Summer
Outs air tmp damped Actual damped Outside Temperature
Summer date / time Date and Time for switch over to Summer Section:
Winter date / time Date and Time for switch over to Winter
5.1.2
Time constant Time constant for damped Outside
Temperature
0…36000 h 24.0 6
Outs air tmp summer If the damped Outside Temperaure > the
this Value => Summer
-64…64 °C 16.0 6
Outs air tmp winter If the damped Outside Temperaure < the
this Value => Winter
-64…64 °C 14 6
17.11 Inputs
17.11.1 Temperatures
Main Index > Unit > Inputs > Temperatures
Parameter Function Value range Unit Standard R S Link
Room Room temperature 1 -64…64 °C x
Room 2 Room temperature 2 -64…64 °C x
Exhaust air Exhaust air temperature -64…64 °C x
Supply air Supply air temperature -64…64 °C x
Outside air Outside air temperature -64…64 °C x
Extract air Extract air temperature -64…64 °C x Section:
Hrec supply air Heat recovery supply air temperature -64…64 °C x
15.3.2
Heat recovery water Heat recovery water temperaure -64…64 °C x
Heating frost Heating frost protect temperature -64…64 °C x
Heating 2 frost Heating 2 frost temperature -64…64 °C x
Supply air 2 Supply air 2 temperature (needed if Extra
Htg and/or Extra Clg have own sequence
-64…64 °C x
Auxiliary Auxiliary Temperature -64…64 °C x
17.11.2 Pressures/Flows
Main Index > Unit > Inputs > Pressures/Flows
Parameter Function Value range Unit Standard R S Link
Supply pressure Supply pressure 0…5000 Pa x
Supply air flow Supply air flow 0…40000 l/s x Section:
Return pressure Return pressure 0…5000 Pa x
15.3.3
Basis Document Siemens Climatix Control System
BDCX.100820.01GB
Page 189

Table of Contents

Other manuals for Siemens Climatix Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Climatix Series and is the answer not in the manual?

Siemens Climatix Series Specifications

General IconGeneral
ApplicationHVAC control
Communication ProtocolsBACnet, Modbus, KNX
InputsAnalog and digital inputs
OutputsAnalog and digital outputs
User Interfaceweb interface
Power Supply24 V AC
Protection ClassIP20
MountingDIN rail mounting