115 / 244 
Siemens  Standard application AHU  CE1P3977en_02 
Building Technologies  Detail pages: Time switch program  01.02.2010 
Parameter  Range  Function 
Period:Start    (Only available at access level 2). 
Start date for the weekly schedule. 
The entry *,* *.00 means that the weekly sched-
ule is always enabled. ---> Enable weekly 
schedule. 
Period:Stop    (Only available at access level 2). 
Start date and time for when the weekly sched-
ule no longer applies. 
 
 
8.3  Day scheduler 
 
 
Parameter  Range  Function 
Day Schedule   
 
−  Passive 
 
−  Active 
Status of week or exception day in question: 
−  Present week day (system day) does not cor-
respond to the processed day. 
−  Present week day (system day) corresponds 
to the processed day. 
Time 1     Special case: This entry may not be adjusted; it 
must always be set to 00:00 and requires pass-
word level 4 to change. 
Value 1    Switching command for Time 1. 
Time 2    Switching time 2. 
*: * ---> Entry disabled. 
Value 2 ... Value 6    Analog value 1. 
Time 3 ... Time 6    Analog time 2. 
 
 
8.4  Calendar (exception and fixed off) 
 
Exception days are defined in the calendars. These may include certain days, peri-
ods or days of the week. On the exception days, the exception days override the 
weekly schedule. 
The plant switches per the weekly scheduler under the exceptions set in the daily 
schedule when an entry is enabled in the calendar exception.  
The plant switches off when the entry calendar fix Off is enabled. 
Parameter 
Calendar exception 
Calender fix off 
Basis Document Siemens Climatix Control System
BDCX.100820.01GB
Page 115