58 / 244   
Siemens  Standard application AHU  CE1P3977en_02 
Building Technologies  Functions  01.02.2010 
•  From fan control: 
–  Summer compensation [%] (if negative). 
–  Winter compensation [%] (if negative). 
 
•  From humidification: 
–  Fan compensation [%] (Decrease) 
 
•  From air quality control: 
–  Function inverse [%]. 
 
Fan control mode =  Direct or DirectVar. 
 
•  ∑ comp up > 90% ---> If possible step-up of a stage (see Disable comp). 
 
•  ∑ comp up < 10% ---> Remove compensation stage. 
 
•  ∑ comp down > 90% ---> Step-down of a stage (Stage 1 is the minimum). 
 
•  ∑ comp down < 10% ---> The removed stage is enabled again. 
 
Fan control mode <> Direct or DirectVar. 
Calculates maximum compensation (100 % compensation): 
Highest stage setpoint + Max forcing – Stage1 Setpoint with fixed minimum 
limit at Stage 1 setpoint and maximum limit at Stage max + Max forcing. 
∑ comp up  80% 
Fan control mode  Pressure 
TSP steps  3 
Stage1 Setpoint  500 Pa 
Stage2 Setpoint  800 Pa 
Stage3 Setpoint  1000 Pa 
Max forcing  200 Pa 
Active stage setpoint  Stage1, 500 Pa 
 
–  Maximum compensation = 1000 + 200 – 500 = 700 [Pa] 
–  Compensation setpoint = Setpoint stage1 + 80 % of maximum compensation.  
= 500 + 700 * 0,8 = 500 + 560 = 1060 [Pa] 
–  Maximum possible setpoint = Stage3 setpoint + max force.  
= 1000 + 200 = 1200 [Pa] 
 
∑ comp down  30% 
Fan control mode  Pressure 
TSP steps  3 
Stage1 Setpoint  500 Pa 
Stage2 Setpoint  800 Pa 
Stage3 Setpoint  1000 Pa 
Max forcing  200 Pa 
Active stage setpoint  Stage2, 800 Pa 
 
–  Maximum compensation 1000 Pa + 200 Pa – 500 Pa = 700 Pa.  
 
–  Setpoint = Setpoint stage2 - 30 % of maximum compensation. 
–  = 800 - 700 * 0.3 = 800 - 210 = 590 [Pa] 
 
–  Minimum possible setpoint = Stage 1 setpoint = 500 Pa, since the setpoint com-
pensation is limited to this value. 
 
 
Staged fans 
Analog fans 
Example 1 
Example 2 