181 / 244 
Siemens  Standard application AHU  CE1P3977en_02 
Building Technologies  HMI  01.02.2010 
Main Index > Configuration > Configuration 2 
Parameter  Function  Value range  Unit  Standard  R  S  Link 
Damper fdbk  Damper Feedback 
Supply Damper fdbk (combined=1fdbk) 
Exhaust Damper fdbk  
No 
One 
Two 
  No    4   
Fan steps freq conv  Additionally digital Outputs for Frequency 
controlled Fans 
1step = Enable signal for FreqConv 
2/3steps = extra DO’s can be used to switch 
somthing according to the Fan step 
 
 
1Step 
2Steps 
3Steps 
  1St    4   
Flow display   
Analog Input for Sensor to see the actual 
Flow without any controlled Function 
Analog Output for actual flow Value 
No 
Yes 
 
Yes+Outp 
  No    4   
Fan steps type  Select hardware configuration of DO’s for 
Fans 
Sep = Single Output per Fan and Step 
SepCombine = Single Output St1 per Fan, 
St2 and Step3 one Output per Step for both 
Fans 
Binary= Single Outputs per Fan but binary 
coded St3 = both DO per Fan are active 
 
 
Sep 
SepCombine 
 
 
Binary 
  Sep    4   
Fan alarm  Combination and Type of Fan alarms 
Combined = one alarm for both Fans 
Supply = only Supply Fan alarm 
Exhaust = only Exhaust fan alarm 
Sply+Exh= two separate alarms 
No 
Combined 
Supply 
Exhaust 
Sply+Exh 
  No    4   
Fan fdbk  Combination and Type of Fan Feedback 
Combined = one fdbk for both Fans 
Supply = only Supply Fan fdbk 
Exhaust = only Exhaust fan fdbk 
Sply+Exh= two separate fdbk’s 
No 
Combined 
Supply 
Exhaust 
Sply+Exh 
  No    4   
Fan deviation alarm  Alarm if the Pressure/Flow Setpoint is not 
reached 
Supply = only Supply deviation alarm 
Exhaust = only Exhaust deviation alarm 
Sply+Exh= Supply and Exhaust deviation 
alarms 
No 
 
Supply 
Exhaust 
Sply+Exh 
  No    4   
Fan cmp room tmp  Fan compensation according to Room or 
Exhaust Temperature (only possible with 
Room or Exhaust air sensor) 
No 
Yes 
  No    4   
Fan cmp air qual  Fan compensation according to Airquality 
Control 
No/Yes    No    4   
Fan cmp humidity  Fan compensation according to Humidity 
control 
           
Fan cmp outs tmp  Fan compensation according to Outside 
Temperature 
(only possible with Outside temperature 
sensor) 
No/Yes    No    4   
Fan htg / clg  Influence the Fan according to the 
Temperature sequence 
Htg = influence as Heating Sequence 
Clg = influence as Cooling Sequence 
Htg+Clg = influence as Htg and Clg 
Sequence 
 
No 
Htg 
Clg/ 
Htg+Clg 
  No    4  Section: 
 15.2 
Tmp stpt selection  Setpoint selection for Cascade controller 
Htg Setpoint + DB = Clg Setpoint 
Separate Htg and Clg Setpoint 
Basic Setpoint + ½ DB = Clg; - ½ DB = Htg 
Clg Setpoint – DB = Htg Setpoint 
 
HtgSpv+Dz 
HtgClgSpv 
Spv+HalfDz 
ClgSpv-Dz 
  HtgSpv+DB 
 
  4   
Ext stpt function  Shift +/- x degrees of the Temperature 
Setpoint 
Override the Setpoint 
Shift 
 
Override 
  Shift    4   
Room tmp mix  Select the valid Room temperature for 
controlling 
(only possible if more than one Room 
temperature available) 
Average 
Minimum 
Maximum. 
RoomSnsr1 
RoomSnsr2 
RoomUnit1 
RoomUnit2 
  Average       
Room draught limit  No = The setted Min/Max Values from the 
Temperature Cascade controller are Valid 
FlowLim = you can set a max allowed 
temperaturedeviation between the Supply 
Air  and the Room temperature 
No 
 
FlowLim 
  No       
Sequence fan clg  Fan Cooling order in Sequence (only 
possible if Clg is selected) 
Fan-Clg 
Clg-Fan 
  Fan-Clg    4   
Basis Document Siemens Climatix Control System
BDCX.100820.01GB
Page 181