56 / 244   
Siemens  Standard application AHU  CE1P3977en_02 
Building Technologies  Functions  01.02.2010 
 
–  Main Index > Unit > Fan Control > Summer comp 
–  Main Index > Unit > Fan Control > Winter Comp 
 
Parameter  Range  Function 
Outside tmp start  -64…64 [°C]  Outside air temperature at which point the compensation begins to 
act. 
Outside tmp end  -64…64 [°C]  Outside air temperature by which the maximum (summer) or mini-
mum setpoint is reached. 
Delta  -100…100 [%]  Fan setpoint compensation relating to the maximum allowed fan 
compensation (See Fan compensation as well). 
 
Setpoint compensation is not undertaken during the summer and winter when the 
outside air temperature sensor fails. Minus value means that the fan is decreased, 
plus value means that the fan is increased. 
For Fan control mode = Direct, DirectVar, the delta must be set to -100% or 100% 
due to that a switch up or down takes place when the total added compensations is 
above 90% (switch back at 10%), but could be less if other compensations is 
active. 
 
 
5.4.5  SupplyFan / Exhaust fan Deviation alarms 
 
–  Main Index > Configuration > Configuration 1 > Fan control mode <> Direct, 
DirectVar oder FixedSpd 
–  Fan deviation alarm must be enabled: 
Main Index > Configuration > Configuration 2 > Fan deviation alarm <> No 
 
Setpoint/actual value monitoring of air control: An alarm is triggered for the follow-
ing cases when the air pressure (or dws volume) deviates from the setpoint during 
a certain period: 
–  Actual value < Min Limit (Is also used as feedback if act value > Min limit, for 
example to enable electrical heating) 
–  Actual value > Setpoint + maximum. 
–  Actual value < Setpoint – maximum. 
–  When setpoint – maximum < Min Limit, Min Limit applies as the comparison 
value. 
 
–  Main Index > Unit > Fan Control > Supply Fan > Setpoints/Settings > Deviation 
alarm 
–  Main Index > Unit > Fan Control > Exhaust fan > Setpoints/Settings > Deviation 
alarm 
 
Parameter  Range  Function 
Alarm  –  Passive  Alarm state. Go to settings page for digital alarms. Set all 
Setpoint compensation 
during the winter. 
Parameterization 
Note 
Prerequisites 
Function 
Function (cont.) 
Parameterization 
Basis Document Siemens Climatix Control System
BDCX.100820.01GB
Page 56