Commissioning and Diagnostics
6-2
Distributed I/O Device ET 200M
EWA-4NEB780600602-06
6.1.1 Prerequisites for Commissioning
Software Prerequisites
Table 6-1 Software prerequisites for commissioning
Configuration
Software Used
Version Notes
STEP 7 – If you configure the IM 153-x from the STEP 7 hardware
catalog, unlimited S7 functionality is available to you
(for example, removal/insertion interrupts on the DP
master for module change during operation or forwarding
of the parameterization data to the FM or HART modules)
If you can’t find your IM 153-x version in the hardware
catalog, integrate the device master file in STEP 7.
COM PROFIBUS w Version 3.0 You have integrated the IM 153-x together with the device
master file in the COM PROFIBUS.
COM PROFIBUS supports the device master file up to
revision 2.
You can use the device master file revision w 3 for
configuration, but the new functions of the IM 153-2Bx00
are then not supported.
1
Configuration software
for DP master used
– You integrate the device master file of the DP slave.
1 The functions which can be operated with the individual device master file revisions are listed in Table 6-4.
You can find the current device master file on the Internet at
http://www.ad.siemens.de/csi_e/gsd.