Configuration Options with the ET 200M
3-23
Distributed I/O Device ET 200M
EWA-4NEB780600602-06
2. The item of identification data assigned to the respective index can be found
under the associated data record number (see Table 3-3).
All data records with identification data have a length of 64 bytes.
The data records are structured in the way shown in Table 3-2.
Table 3-2 Structure of data records with identification data
Contents
Length (bytes) Code (hex)
Header information
SSL ID 2 F1 11
Index 2 00 0x
Length of identification data 2 00 38
Number of blocks with identification data 2 00 01
Identification data
Index 2 00 0x
Identification data for respective index (see
Table 3-3)
54