Configuration Options with the ET 200M
3-8
Distributed I/O Device ET 200M
EWA-4NEB780600602-06
3.4.2 Time Stamping with 3 ms Accuracy
Prerequisites
The following configuration is permitted for time stamping with 3 ms accuracy:
IM 153-2 (as of 6ES7 153-2Bx00-0XB0)
DI modules
SM 321; DI 16 x 24 V DC; with diagnostics
6ES7 321-7BHx0-0AB0
The synchronization interval must be set to 10 seconds.
Rules
The following rules must be observed:
The accuracy level applies throughout the entire station.
A station can have a maximum of 128 DI modules.
The parameterized input delay must be identical for all DI modules.
No analog signals are processed in the station.
No CP or FM modules are permitted in the station.
3.4.3 Time Synchronization with Flexible Time Interval
The synchronization interval can be set in the configuration tool.
The longer the set synchronization interval is, the lower the accuracy of time
stamping will be.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Other manuals for Siemens SIMATIC ET 200M

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC ET 200M and is the answer not in the manual?

Siemens SIMATIC ET 200M Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC ET 200M
CategoryI/O Systems
LanguageEnglish

Related product manuals