Commissioning
S7-300 Programmable Controller Hardware and Installation
A5E00105492-01
8-21
Monitoring variables
You have two options of monitoring variables:
updating the status values once via menu item Variable > Update status
values
or
continuous update of status values via menu item Variable > Monitor
Controlling variables
To control variables, proceed as follows:
1. Left-click the field Control value of the respective variable.
2. Enter the control value according to the data type.
3. To update control values once, select the menu item Variable > Enable control
values.
or
Enable control values permanently via menu item Variable > Control.
4. In the Monitor test function, verify the control value entry in the variable.
Is the control value valid?
You can disable the control value entered in the table. An invalid value is displayed
same as a comment. You can re-enable the control value.
Only valid control values can be enabled.
Setting the trigger points
Trigger points:
The "Trigger point for monitoring" determines the time of update for values of
variables to be monitored.
The "Trigger point for controlling" determines the time for assigning the control
values to the variables to be controlled.
Trigger condition:
The "Trigger condition for monitoring" determines whether to update values
once when the trigger point is reached or continuously every time the trigger
point is reached.
The "Trigger condition for controlling" determines whether to assign control
values once or permanently to the variable to be controlled.
You can customize the trigger points using the tool "Monitor and control variable" in
menu item Variable > Set Trigger ... start.
Special features
If "Trigger condition for monitoring" is set to once , the menu items Variable >
Update status value or Variable > Monitor have the same effect, namely a
single update.
If "Trigger condition for controlling" is set to once , the menu items Variable >
Update control value or Variable > Control have the same effect, namely a
one-time assignment.
If trigger conditions are set to permanent , the said menu items have different
effects as described above.
If monitoring and controlling is set to the same trigger point, monitoring is
executed first.

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)

Related product manuals