Testing functions, Diagnostics and Fault Elimination
S7-300 Programmable Controller Hardware and Installation
10-12 A5E00105492-01
10.6 Diagnostics of DP CPUs
10.6.1 Diagnostics of DP CPUs operating as DP master
Diagnostics evaluation in the user program
The figure below shows you the procedure for evaluating the diagnostics in the
user program.
Diagnostic event
OB82 is called
Enter Bit 0 of the
as Bit 15 in the
OB82_IO_FLAG
OB82_MDL_ADDR
Result: diagnostic address
“OB82_MDL_ADDR*”
Read out OB82_MDL_ADDR
and
Read out
(= identifier I/O module)
OB82_IO_FLAG
For the diagnosis of the
components involved:
SFB 54call
(in DPV1 environment)
MODE =1 set
Diagnostic data is entered
in the TINFO and
AINFO parameters.
Note:
The SFC 13 is asynchronous, i. e. It can
be called several times if necessary until
it changes into the BUSY = 0 status.
First call in OB82,
Finish processing in the cycle.
For the diagnosis of the whole DP slave:
SFC 13call
Enter the diagnostic address
“OB82_MDL_ADDR*” in the
LADDR parameter
For the diagnosis of the modules involved:
SFC 51call
Enter the diagnostic address
“OB82_MDL_ADDR*” in the
Enter the SZL_ID
p (= diagnostic data of a module)
INDEX parameter
ID W#16#00B3 in the
arameter
318-2-DP>=V3.0.0
Figure 10-3 Diagnostics with CPU 31x-2 (315-2-DP as of 315-2AF03)

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)

Related product manuals