Commissioning
S7-300 Programmable Controller Hardware and Installation
8-26 A5E00105492-01
8.7.2 Commissioning the CPU as DP Master
Prerequisites for commissioning
The PROFIBUS subnet has been configured.
The DP slaves are ready for operation (see relevant DP slave manual).
An MPI/DP interface as DP interface must be configured accordingly (only CPU
318-2).
You must configure the CPU as DP master prior to commissioning. That is, in
STEP 7 you must:
configure the CPU as a DP master,
assign a PROFIBUS address to the CPU,
assign a master diagnostic address to the CPU,
integrate the DP slaves into the DP master system.
Is a CPU 31x-2 DP/31xC-2 DP a DP Slave?
If so, you will find that DP slave in the PROFIBUS-DP catalog as already
configured station. In the DP master, assign a slave diagnostic address to
this DP Slave CPU. You must interconnect the DP master with the DP slave
CPU and specify the address areas for data exchange with the DP slave
CPU.
Commissioning
Commission CPU 31x-2 DP/31xC-2 DP as DP master in the PROFIBUS subnet as
follows:
1. Download the PROFIBUS subnet configuration (preset configuration) you have
created in STEP 7 from the PG to CPU 31x-2 DP/31xC-2 DP.
2. Switch on all of the DP slaves.
3. Switch CPU 31x-2 DP/31xC-2 DP from STOP to RUN mode.

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)

Related product manuals