Testing functions, Diagnostics and Fault Elimination
S7-300 Programmable Controller Hardware and Installation
A5E00105492-01
10-23
Station status 1
Table 10-13 Structure of station status 1 (Byte 0)
Bit Description Remedy
0 1: DP slave cannot be addressed by DP master. Is the correct DP address set on the DP
slave?
Is the bus connector in place?
Does the DP slave have power?
Correct configuration of the RS485
Repeater?
Perform a reset on the DP slave.
1 1: DP slave is not ready for data exchange. Wait for the slave to complete startup.
2 1: Configuration data sent by DP master to the DP
slave is inconsistent with slave configuration.
Was the software set for the correct
station type or DP slave configuration?
3 1: Diagnostic interrupt, generated by CPU RUN to
STOP transition
0: Diagnostic interrupt, generated by CPU STOP to
RUN transition
You can read the diagnostic data.
4 1: Function not supported; e.g. changing the DP
address at software level
Check configuration data.
5 0: This bit is always "0". -
6 1: DP slave type inconsistent with software
configuration.
Was the software set for the right station
type? (parameter assignment error)
7 1: DP slave was configured by a DP master other
than the master currently accessing the slave.
The bit is always 1 if, for example, you are
currently accessing the DP slave via PG or
a different DP master.
The configuring master's DP address is
located in the "Master PROFIBUS address"
diagnostics byte.
Station Status 2
Table 10-14 Structure of Station Status 2 (Byte 1)
Bit Description
0 1: The DP slave requires new parameters and configuration.
1 1: A diagnostic message was received. The DP slave cannot resume operation until the error
has been cleared (static diagnostic message).
2 1: This bit is always "1" if a DP slave exists with this DP address.
3 1: The watchdog monitor is enabled on this DP slave.
4 1: DP slave has received control command "FREEZE".
5 1: DP slave has received control command "SYNC".
6 0: This bit is always "0".
7 1: DP slave is disabled, that is, it has been excluded from cyclic processing.

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)

Related product manuals