Appendix
S7-300 Programmable Controller Hardware and Installation
A5E00105492-01
11-15
compatibility (EMC). The table contains information on the general rules governing
clearances to enable you to choose the right cables.
How to Read the Table
To find out how to run two cables of different types, proceed as follows:
1. Look up the type of the first cable in column 1 (Cables for ...).
2. Look up the type of the second cable in the corresponding field in column 2
(and Cables for ...).
3. Read off the guidelines to be observed from column 3 (Run ...).
Table 11-7 Cable routing inside buildings
Cables for ... and cables for ... Run ...
Bus signals, shielded
(PROFIBUS)
Data signals, shielded
(programming devices,
operator panels, printers,
counter inputs, etc.)
Analog signals, shielded
DC voltage ( 60 V),
unshielded
Process signals ( 25 V),
shielded
AC voltage ( 25 V),
unshielded
Monitors (coaxial cable)
In common bundles or cable
ducts
DC voltage (> 60 V and
400 V), unshielded
AC voltage (> 25 V and
400 V), unshielded
In separate bundles or cable
ducts (no minimum clearance
necessary)
Bus signals, shielded
(PROFIBUS)
Data signals, shielded
(programming devices,
operator panels, printers,
counter inputs, etc.)
Analog signals, shielded
DC voltage ( 60 V),
unshielded
Process signals ( 25 V),
shielded
AC voltage ( 25 V),
unshielded
Monitors (coaxial cable)
DC and AC voltage (> 400 V),
unshielded
inside cabinets:
In separate bundles or cable
ducts (no minimum clearance
necessary)
outside cabinets:
On separate cable racks with a
clearance of at least 10 cm

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)

Related product manuals