Commissioning
S7-300 Programmable Controller Hardware and Installation
A5E00105492-01
8-29
8.7.3 Commissioning the CPU as DP slave
Prerequisites for commissioning
The DP master is configured and programmed.
If the MPI/DP interface of CPU 318-2 DP is to be operated as DP interface, you must
configure the interface accordingly.
You must program and configure CPU 31x-2 DP/31xC-2 DP as DP slave prior to
commissioning. That is, in STEP 7 you must:
"switch on" the CPU as DP slave,
assign a PROFIBUS address to the CPU,
assign a slave diagnostic address to the CPU,
specify whether the DP master is an S7 DP master or another DP master,
specify the address areas for data exchange with the DP master.
All other DP slaves are programmed and configured.
GSD Files
When working on an IM 308-C or non-Siemens system, you require a GSD file in
order to be able to configure CPU 31x-2 DP/31xC-2 DP as DP slave in a DP
master system.
COM PROFIBUS as of V 4.0 includes this GSD file.
When working with an older version or another configuration tool, you can
download the GSD file under:
Internet URL http://www.ad.siemens.de/csi/gsd
or
via modem from the SSC (Interface Center) Fürth, Germany; Phone number (0911)
911/737972
Configuration and parameter assignment message frame
STEP 7 supports you in configuring/programming CPU 31x-2 DP/31xC-2 DP.
Should you require a description of the configuration and parameter assignment
frame, in order to use a bus monitor for example, you can find it on the Internet at
http://www.ad.siemens.de/csinfo under article ID 1452338.

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)

Related product manuals