Configuring
S7-300 Programmable Controller Hardware and Installation
A5E00105492-01
4-45
Example: Terminating resistor in the MPI subnet
The figure below shows you an example of an MPI subnet and where to install the
terminating resistance.
Terminating resistor on
S7-300
Spur line
OP 27
OP 27
PG
PG*
* connect via spur line only during commisioning / maintenance
RS 485-
Repeater
S7-300
SF
BUSF
DC5V
FRCE
RUN
STOP
SIEMENS
SF
BUSF
DC5V
FRCE
RUN
STOP
SIEMENS
S7-300
SF
BUSF
DC5V
FRCE
RUN
STOP
SIEMENS
S7-300
SF
BUSF
DC5V
FRCE
FRCE
RUN
STOP
SIEMENS
Figure 4-19 Activation of the terminating resistors in an MPI subnet
Warning
Disturbance of data traffic might occur on the bus.
A bus segment must always be terminated at both ends with the terminating
resistor. This, for example, is not the case if the last slave with bus connector is off
power.
Since the bus connector draws its power from the station, the terminating resistor
has no effect.
Please make sure that power is always supplied to stations on which the
terminating resistor is active.
As an alternative, you can also use the PROFIBUS Terminator as active bus
termination.

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)

Related product manuals