Wiring
S7-300 Programmable Controller Hardware and Installation
6-10 A5E00105492-01
Wiring the front connector
Table 6-6 Wiring front connectors
Step 20-pin front connector 40-pin front connector
1. Thread the cable strain relief into the front
connector.
Do you want to exit the cables at the bottom of the module?
If yes:
Starting at terminal 20, work your way down
to terminal 1.
Starting at terminal 40 or 20, wire the connector,
working in alternating passes from terminals 39,
19, 38, 18 etc.until you have reached
terminals 21 and 1.
2.
If not:
Starting at terminal 1, work your way up to
terminal 20.
Starting at terminal 1 or 21, wire the connector,
working in alternating passes from terminals 2,
22, 3, 23 etc.until you have reached
terminals 20 and 40.
3. Front connectors with screw terminals:
Screw-tighten unused terminals also.
4. Attach the cable strain-relief assembly around
the cable and the front connector.
5. Pull the cable strain-relief assembly tight. Push in the strain relief retainer to the left to improve
utilization of the available cable space.
1
2
0.5 Nm to
0.8 Nm
1
2
4
3
0.4 Nm to
0.7 Nm

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)

Related product manuals