Appendix
S7-300 Programmable Controller Hardware and Installation
A5E00105492-01
11-23
11.3.4 Rules for the transition points between lightning protection
zones 1 <-> 2 and higher
Rules for transition points 1 <-> 2 and higher (local equipotential bonding)
The following measures must be taken on all transition points 1 <-> 2 and higher:
Set up local equipotential bonding at each subsequent lightning protection zone
transition.
Include all lines (also metal conduits, for example) in the local equipotential
bonding of all subsequent lightning protection zone transition points.
Include all metal installations located within the lightning protection zone in the
local equipotential bonding (for example, metal part within lightning protection
zone 2 at transition 1 <-> 2).
Additional Measures
We recommend fine-wire fusing for following elements:
All 1 <-> 2 and greater lightning protection zone transitions
All cables that run within a lightning protection zone and are longer than 100 m
Lightning protection element for the 24 VDC power supply module.
Always use the Blitzductor VT, type AD 24 V SIMATIC for the 24 VDC power
supply module of the S7-300. All other surge protection components do not meet
the required tolerance range of 20.4 V to 28.8 V of the S7--300 power supply.
Lightning Conductor for Signal Modules
You can use standard surge protection components for the digital I/O modules.
However, please note that these only permit a maximum of 26.8 V for a rated
voltage of 24 VDC. If the tolerance of your 24 VDC power supply is higher, use
surge protection components with 30 VDC rating.
You can also use Blitzductor VT, type AD 24 V. Note that input current can
increase if negative input voltages are generated.
Low-voltage protection elements for 1<-> 2
For the transition points between lightning protection zones 1 <-> 2 we recommend
the surge protection components listed in the table below. This low-voltage
protection must be used in S7-300 for CE compliance.

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)

Related product manuals