S7-300 Programmable Controller Hardware and Installation
A5E00105492-01
11-31
Risks
In all cases where the occurrence of failures can result in material damage or injury
to persons, special measures must be taken to enhance the safety of the
installation - and therefore also of the situation. System-specific and special
regulations exist for such applications. They must be observed on installing the
control system (e.g. VDE 0116 for burner control systems).
For electronic control equipment with a safety function, the measures that have to
be taken to prevent or rectify faults are based on the risks involved in the
installation. As of a certain degree of hazard the basic measures mentioned above
are no longer sufficient. That is, additional measures (e.g. redundant
configurations, tests, checksums etc.) must be implemented and certified for the
control equipment (DIN VDE 0801). The prototype of the fail-safe PLC S5-95F was
tested by TÜV (German Institute for Technological Surveillance), BIA and G EM III;
several certificates have been granted. Thus, it is suitable in the same way as the
previously tested fail-safe PLC S5-115F to control and monitor safety-relevant
system areas.
Splitting the group into safety-relevant areas and areas which are not safety
relevant
Most plants contain equipment performing safety-relevant operations (e.g.
EMERGENCY-OFF switch, protective gates, two-hand controls). To avoid the need
to examine the entire controller from the aspect of safety, the controller is usually
divided into an area that is safety-relevant and an area that is not safety-
relevant In the non-safety-related area, no special demands are placed on the
safety of the control equipment because any failure in the electronics will have no
effect on the safety of the installation. In the safety-relevant area, however, it is
only allowed to operate controllers or circuits compliant with corresponding
regulations.
The following divisions are common in practical situations:
For control equipment with few safety-related functions (e.g. machine controls)
The conventional PLC is responsible for machine control, whereas safety-
related functions are implemented with a fail-safe mini PLC (e.g. S5-95F).
For controllers with balanced areas (e.g. chemical installations, cable cars)
In this case also, the area that is not safety-relevant is controlled with a
standard PLC, whereas a tested fail-safe controller (S7-400F, S7-400FH, S5-
115F, or multiple S5-95F) controls the safety-relevant areas.
The entire installation is implemented with a fail-safe control system.
For control equipment with mainly safety-relevant functions (e.g. burner control
systems)
The entire control system is implemented with fail-safe technology.

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)