EasyManua.ls Logo

Siemens Simatic S7-300 - Page 277

Siemens Simatic S7-300
594 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Analog modules
6.6 Analog input module SM 331; AI 8 x 13 Bit;(6ES7331-1KF01-0AB0)
S7-300 Automation System Module data
Manual, 08/2006, A5E00105505-04
6-43
Technical data
Technical data
Dimensions and weight
Dimensions W x H x D (mm) 40 x 125 x 117
Weight Approx. 250 g
Module-specific data
Isochronous mode supported No
Number of inputs
with resistive transducers
8
8
Cable length
Shielded
max. 200 m
max. 50 m at 50 mV
Voltages, currents, electrical potentials
Constant current for resistive transducers
Resistance thermometer and resistance
measurements 0 ... 600 Ω
Resistance measurement 0 ... 6 kΩ
max. 0,83 mA
max. 0,25 mA
Electrical isolation
between channels and the backplane bus
between channels
Yes
No
Permissible potential difference
between inputs (C
MV
)
Between the inputs and M
internal
(V
iso
)
2,0 VDC
75 VDC / 60 VAC
Insulation test voltage 500 VDC
Current consumption
from the backplane bus
max. 90 mA
Power loss of the module typ. 0.4 W
Formation of analog values
Measuring principle Integrating
Integration/conversion time/resolution (per channel)
programmable
Yes
Noise cuppression at interference frequency f1 in Hz
50 60
Integration time in ms
60 50
Basic conversion time, including the integration time in ms
66 55
Additional conversion time for resistance measurements in ms 66 55
Resolution in bits (including overshoot range)
13 bits 13 bits
Noise suppression, error limits
Noise suppression at f = n (f1 ± 1 %), (f1 = interference frequency) n=1.2...
Common-mode noise (CMV < 2 V)
Seriesmode interference (peak value of disturbance < rated
input range)
> 86 dB
> 40 dB
Crosstalk between inputs > 50 dB