EasyManua.ls Logo

Siemens Simatic S7-300 - Page 278

Siemens Simatic S7-300
594 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Analog modules
6.6 Analog input module SM 331; AI 8 x 13 Bit;(6ES7331-1KF01-0AB0)
S7-300 Automation System Module data
6-44 Manual, 08/2006, A5E00105505-04
Technical data
Operational limit (across temperature range, relative to input range)
± 0,6 %
Voltage input
± 5 V
± 10 V
1 V to 5 V
0 V to 10 V
± 50 mV
± 500 mV
± 1 V
± 0,5 %
Current input
± 20 mA
0 mA to 20 mA
4 mA to 20 mA
± 0,5 %
Resistance
0 kΩ to 6 kΩ
0 Ω to 600 Ω
± 0.5 %
± 0.5 %
Pt 100
Ni 100
Standard
± 1,2 K
Pt 100
Ni 100
Klima
± 1 K
Ni 1000,
LG-Ni 1000
Standard
± 1 K
Resistance thermometers
Ni 1000
LG-Ni 1000
Klima
± 1 K
Basic error limit (operational error limit at 25 °C, relative to input range)
± 0,4 %
Voltage input
± 5 V
± 10 V
1 V to 5 V
0 V to 10 V
± 50 mV
± 500 mV
± 1 V
± 0,3 %
Current input
± 20 mA
0 mA to 20 mA
4 mA to 20 mA
± 0,3 %
Resistance
0 kΩ to 6 kΩ
0 Ω to 600 Ω
± 0,3 %
± 0,3 %
Pt 100
Ni 100
Standard
± 1 K
Pt 100
Ni 100
Klima
± 0.8 K
Ni 1000
LG-Ni 1000
Standard
± 0.8 K
Resistance thermometers
Ni 1000
LG-Ni
1000 Klima
± 0.8 K