Commissioning   
4.6 Basic parameterization of the drive objects 
  Commissioning with Startdrive 
134  Commissioning Manual, (IH3), 07/2016, 6SL3097-4AA10-0BP0 
●  Startdrive is in the online mode. 
You require master control for the selected drive to perform the motor identification. Master 
control has to be activated before the optimization measurements are started.  
1.  Click the "Activate" button at "Master control". 
The "Activate master control" message window opens. 
2.  Carefully read the warning note and check the value of the monitoring time. 
The monitoring time specifies the time that the connection between the PC and drive is 
cyclically monitored. The minimum value is 1000 ms. 
3.  Click on "Continue" to confirm the monitoring time. 
The message window is closed. The "Stationary/rotating measurement" screen form is 
then active. 
Configuring motor identification 
The measurements available are displayed in the "Measurement type" setting area. Already 
when the screen form is opened, a check is made to determine whether a measurement is 
already active and, if so, it is displayed. If no measurement is selected, a check is made as 
to which measurement has already been performed and then used as recommendation. 
 
Note 
Detailed notes regarding the motor identification 
In "Chapter 4.12 Motor identification" in the Function Manual Drive Functions, you will find 
detailed information about motor data
 identification for various motor types.  
 
Note 
Expert settings 
We only recommend that experienced users manually select the measurement type from the 
list. This means that when required, individual measurements can be repeated.