EasyManua.ls Logo

Siemens SINAMICS S120 - Braking Module in Booksize Format; Additional Modules; Control Supply Module

Siemens SINAMICS S120
226 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Diagnostics
5.2 Diagnostics using LEDs
Commissioning with Startdrive
146 Commissioning Manual, (IH3), 07/2016, 6SL3097-4AA10-0BP0
5.2.2.7
Braking Module in booksize format
Table 5- 10 Meaning of the LEDs on the Braking Module booksize
LED
Color
State
Description, cause
Remedy
READY Off Electronic power supply is missing or outside permissible
tolerance range.
Component deactivated via terminal.
Green Continuous
light
Component is ready to operate.
Red Continuous
light
Enable signal missing (input terminal)
Overtemperature
Overcurrent trip
I
2
t monitoring responded
Ground fault/short circuit
Note:
In the event of an overtemperature, the error cannot be
acknowledged until after a cooling down time.
Diagnose fault (via
output terminals) and
acknowledge it (via
input terminal)
DC LINK Off There is no DC link voltage or the electronic power supply is
missing or outside permissible tolerance range.
Component not active.
Green Flashing
light
Component active (DC link discharge via braking resistor in
progress).
5.2.3
Additional modules
5.2.3.1
Control Supply Module
Table 5- 11 Control Supply Module description of the LEDs
LED
Color
State
Description, cause
Remedy
READY off Electronic power supply is missing or outside permissible
tolerance range.
Green Continuous
light
Component is ready to operate.
DC LINK off Electronic power supply is missing or outside permissible
tolerance range.
Orange Continuous
light
DC link voltage within permissible tolerance range.
Red Continuous
light
DC link voltage outside permissible tolerance range.

Table of Contents

Other manuals for Siemens SINAMICS S120

Related product manuals