Commissioning
4.3 Creating a project
Commissioning with Startdrive
64 Commissioning Manual, (IH3), 07/2016, 6SL3097-4AA10-0BP0
Inserting a device in the network view
Alternatively, you can insert a device in the network view.
1. Open the network view in the project view.
2. Drag and drop the device from the hardware catalog to the network view.
Result
The drive has been inserted.
4.3.4
Inserting an infeed unit
4.3.4.1
Inserting a space holder for an infeed unit
Precondition
A project has been created.
A control module (drive) has been inserted in the device configuration.
Note
Sequence
Generally, the infeed unit is inserted in the configuration immediately after the drive in the
device view. In this case, the i
nfeed unit is also automatically wired to the drive.
You can also insert an infeed unit at a later point in time (for example, after the Motor
Module). The infeed unit is then no longer automatically wired. In this case, you must
manually wire the "infeed
unit" component with the other components (see Chapter "Editing
a DRIVE
-CLiQ connection (Page 70)").
Note
Handling components in the device v
iew is subsequently explained using an infeed unit as
example. The procedure is identical for all other components.