EasyManua.ls Logo

Siemens SINAMICS S120 - Sensor Module Cabinet SMC10; SMC20; Sensor Module Cabinet SMC30

Siemens SINAMICS S120
226 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Diagnostics
5.2 Diagnostics using LEDs
Commissioning with Startdrive
Commissioning Manual, (IH3), 07/2016, 6SL3097-4AA10-0BP0
147
5.2.3.2
Sensor Module Cabinet SMC10 / SMC20
Table 5- 12 Sensor Module Cabinet 10/20 (SMC10/SMC20) description of the LEDs
LED
Color
State
Description, cause
Remedy
RDY
READY
off Electronic power supply is missing or outside permissible
tolerance range.
Green Continuous
light
The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
Orange Continuous
light
DRIVE-CLiQ communication is being established.
Red Continuous
light
At least one fault is present in this component.
Note:
LED is controlled irrespective of the corresponding messag-
es being reconfigured.
Remedy and
acknowledge fault
Green/
red
Flashing
light 0.5 Hz
Firmware is being downloaded.
Flashing
light 2 Hz
Firmware download is complete. Wait for POWER ON Carry out a POWER
ON
Green/
orange
or
Red/
orange
Flashing
light
Component recognition via LED is activated (p0144).
Note:
Both options depend on the LED status when module
recognition is activated via p0144 = 1.
5.2.3.3
Sensor Module Cabinet SMC30
Table 5- 13 Meaning of LEDs on the Sensor Module Cabinet SMC30
LED
Color
Status
Description, cause
Remedy
RDY
READY
Off The electronics power supply is missing or outside the per-
missible tolerance range.
Green Continuous
light
The component is ready for operation. Cyclic DRIVE-CLiQ
communication is taking place.
Orange Continuous
light
DRIVE-CLiQ communication is being established.
Red Continuous
light
This component has at least one fault.
Note:
LED is controlled irrespective of the corresponding messag-
es being reconfigured.
Remedy and
acknowledge fault
Green/
red
Flashing
light 0.5 Hz
Firmware is being downloaded.
Green/
red
Flashing
light 2 Hz
Firmware download is complete. The system waits for
POWER ON.