Diagnostics
5.2 Diagnostics using LEDs
Commissioning with Startdrive
142 Commissioning Manual, (IH3), 07/2016, 6SL3097-4AA10-0BP0
Safety instructions for diagnostic LEDs of the power units
Danger to life if the fundamental safety instructions and residual risks are not carefully
observed
The non-observance of the fundamental safety instructions and residual risks stated in
Chapter 1 can result in accidents with severe injuries or death.
• Adhere to the fundamental safety instructions.
• When assessing the risk, take into account residual risks.
Danger to life when live parts of the DC link are touched
Irrespective of the status of the "DC LINK" LED, hazardous DC link voltages can be
present. This means that the touching of live parts can result in death or serious injury.
• Observe the warning information on the component.
Active Line Module booksize
Table 5- 5 Meaning of the LEDs on the Active Line Module
Off Off Electronic power supply is missing or outside permissible
–
Green Off The component is ready for operation and cyclic DRIVE-CLiQ
communication is taking place.
–
Orange The component is ready for operation and cyclic DRIVE-CLiQ
communication is taking place.
The DC link voltage is present.
–
Red The component is ready for operation and cyclic DRIVE-CLiQ
communication is taking place.
The DC link voltage is too high.
Check the line voltage
DRIVE-CLiQ communication is being established.
Red – At least one fault is present in this component.
LED is controlled irrespective of the corresponding messages
Remedy and acknowledge
fault