Appendix
A.4 System rules, sampling times and DRIVE-CLiQ wiring
Commissioning with Startdrive
206 Commissioning Manual, (IH3), 07/2016, 6SL3097-4AA10-0BP0
A.4.2
System rules
A maximum of 24 drive objects (DOs) can be connected to one Control Unit.
Control Units
The CU320-2 Control Unit is a multi-axis control module for operating Infeed Modules and
Motor Modules in the booksize format. Sensor Modules can also be connected.
Motor Modules/control modes
For the CU320-2 Control Unit the following applies:
The CU320-2 Control Unit is a multi-axis control module for operating Motor Modules in
the booksize format.
For multi-axis modules, each axis counts individually (one Double Motor Module = two
Motor Modules).
Mixed operation of control types:
The following are permitted:
Mixed operation of servo control and V/f control.
The following applies when connecting Motor Modules in parallel:
It is not permissible to connect Motor Modules in parallel.
Line Modules
For the CU320-2 Control Unit the following applies:
Only one drive object of the Smart Line Module (SLM), Basic Line Module (BLM) and
Active Line Module (ALM) types is permitted in each case.
Mixed operation of an Active Line Module with a Smart Line Module (SLM) or with a Basic
Line Module (BLM) is not permitted.
Mixed operation of a drive object of the Smart Line Module (SLM) type with a drive object
of the Basic Line Module (BLM) type is permitted.
Two further Voltage Sensing Modules can be operated with the "network transformer"
function module for Active Line Modules (ALM).
The following applies to parallel connection of Line Modules:
Parallel connection is permitted for Infeed Modules in the chassis format and for Active
Line Modules (ALM) from the 120 kW performance class for the booksize format.
A maximum of four Infeed Modules are permitted within a parallel connection.
In booksize format, a maximum of two Active Line Modules (ALM) from the 120 kW
performance class are permitted within a parallel connection.
The operation of Infeed Modules with different performance values is not permitted within
a parallel connection.