Commissioning
4.6 Basic parameterization of the drive objects
Commissioning with Startdrive
Commissioning Manual, (IH3), 07/2016, 6SL3097-4AA10-0BP0
133
4.6.4.2
Stationary/rotating measurement
Motor identification (MotID) provides a means of determining motor data (of third-party
motors, for example). To improve control properties of the motor, the MotID should be
performed. The main motor identification components are the stationary and rotating
measurements.
Measurement
type
Selecting the measurement type (for experts)
Configuration
Entering the configuration data and starting the measurement
Status
Indicates measurement progress
Measurement
result
Displays the measurement results of the MotID. The measurement results can be
corrected or accepted.
Figure 4-58 Stationary/rotating measurement
Note
If a power on or a warm restart is performed when the motor data identification is selected,
then the motor data identification request
is lost. A requested motor data identification must
be reselected manually after powering up.
Note
As long as a rotating measurement has been selected and is running, you cannot perform
any upload, download, RAM to ROM or reset to the factory settings
.
NOTICE
Damage to the device as a result of incorrectly selected rated current and/or maximum
current values
Incorrect rated current or maximum current data can destroy the motor!
Check that the current values that have been entered are correct.