Appendix
A.4 System rules, sampling times and DRIVE-CLiQ wiring
Commissioning with Startdrive
Commissioning Manual, (IH3), 07/2016, 6SL3097-4AA10-0BP0
215
Encoder, Sensor Modules
The motor encoder or Sensor Module should be connected to the associated Motor
Module.
Connecting the motor encoder via DRIVE-CLiQ:
Single Motor Module Booksize to terminal X202
Double Motor Module Booksize motor X1 to terminal X202 and motor X2 to terminal
X203
If possible, Sensor Modules of direct measuring systems should not be connected to the
DRIVE-CLiQ line of Motor Modules, but rather to free DRIVE-CLiQ sockets of the Control
Unit.
Note
This restriction does not apply t
o star-type connections for the Motor Modules.
Voltage Sensing Modules
The Voltage Sensing Module (VSM) should be connected to the DRIVE-CLiQ socket
X202 (booksize format) of the associated Line Module/Motor Module.
If the DRIVE-CLiQ socket X202/X402 is not available, a free DRIVE-CLiQ socket on
the Line Module/Motor Module should be selected.
Figure A-1 Example of a topology with VSM for booksize components
Terminal Modules
Terminal Modules should be connected to DRIVE-CLiQ socket X103 of the Control Unit in
series.
If possible, Terminal Modules should not be connected to the DRIVE-CLiQ line of Motor
Modules, but rather to free DRIVE-CLiQ sockets of the Control Unit.
Note
This restriction does not apply to star
-type connections for the Motor Modules.