Note
Use 75 °C wire for an ambient temperature of 40 °C or less and use 90 °C wire for ambient 
temperature between 40 °C and 60 °C.
A correction factor of K = 0.71 has been used based on the following:
A maximum of four cables are laid side by side on a cable ladder.
The ambient temperature during cable operation is 30 °C.
(in accordance with EN 60204-1 and IEC 364-5-523)
 
 
Conductor cross-sections of the DI/DO, AI/AO terminal connecting cable 
Table 5-8 Conductor cross-sections of the DI/DO, AI/AO terminal connecting cable 
  DO (Digital Outputs) DI (Digital inputs) AI (Analog inputs) AO (Analog outputs)
Limit value (mm
2
) ≤ 1.2  ≥ 0.1 ≥ 0.1 ≥ 0.1
Recommended value (mm
2
) 1.0 0.25 0.25 0.25
 
 
NOTICE
To ensure that input/output precision is ≤ 1 %, it's recommended that the cable length be 
less than (<) 5 m. If you don't have this precision requirement, use a cable which is less than 
(<) 30 m.
 