NOTICE
"P" of parameters in quick commissioning is followed by a ".", for example, P.0304 and P.
1080.
Motor parameters can only be set in "Operation mode ① - Quick motor data setting 
(Page 66)", but in "Operation mode⑤ - Acess all the parameters", all the motor parameters 
except for P0305 are read-only.
 
Motor data
In SINCAMICS V10, the factory default motor parameter values are set based on SIEMENS 
1LG0 4-pole AC motors. (See table below for default motor data settings of SIEMENS 1LG0 
4-pole AC motors.) You can change the defaults against data shown on the rating plate of your 
motor connected.
SIEMENS 1LG0 4-pole AC motors
Rated inverter 
output power (kW)
Motor 
frame 
size
Motor Type Rated speed 
(rpm)
Rated motor 
efficiency
 (%)
Power 
factor
Rated 
current (A)
Rated 
torque 
(Nm)
0.55 80M 1LG0080-4AA.. 1390 71.0 0.750 1.57 3.8
0.75 80M 1LG0083-4AA.. 1380 73.0 0.760 2.05 5.2
1.1. 90S 1LG0090-4AA.. 1390 76.2 0.760 2.89 7.6
1.50 90L 1LG0096-4AA.. 1390 78.5 0.790 3.67 10.3
2.20 100L 1LG0106-4AA.. 1410 81.0 0.800 5.16 14.9
3.00 100L 1LG0107-4AA.. 1410 82.8 0.810 6.80 20.3
4.00 112M 1LG0113-4AA.. 1435 84.5 0.820 8.80 26.6
5.50 132S 1LG0130-4AA.. 1440 86.0 0.820 11.80 36.5
7.50 132M 1LG0133-4AA.. 1440 87.2 0.840 15.60 49.7
11.00 160M 1LG0163-4AA.. 1460 89.0 0.830 22.60 72.0
15.00 160L 1LG0166-4AA.. 1460 90.0 0.840 30.10 98.1
18.50 180M 1LG0183-4AA.. 1470 90.6 0.860 36.10 120.2
22.00 180L 1LG0186-4AA.. 1470 91.4 0.860 42.50 143.0
Commissioning 
6.4 Quick commissioning
SINAMICS V10
64 Operating Instructions, 08/2011, A5E03453178 (this is not an order number)