Siemens SINAMICS V10 - Connection Mode C10

Siemens SINAMICS V10
124 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Par. No. Parameter name Range Unit Default
P0703 Function of digital input 3 0 - 99 - - 11
P1000 Selection of frequency setpoint 0 - 53 - - 2
P0725 PNP/NPN digital inputs 0 - 1 - - 1
* "xx" means current application macro.
Typical connection mode 10 (C10)
Description:
1. In LOC mode, motor start/stop, rotation direction and speed can be controlled via the
operator panel.
2. In REM mode, motor start/stop can be controlled via an external signal source connected
to DI1, motor MOP-up/MOP-down via external signal sources connected to DI2 and DI3,
feedback value via an external sensor connected to terminals AI1+ and AI1-.
L1
L2
3 AC 400 V
L3
PE
Fuse
Contactor
Connection macro: C10
ON/OFF Command
RPM Meter
0 - 10 V DC or
0 - 20 mA DC
from Feedback Sensor
N
PE
L1
L3
L2
M
3~
U
V
W
5
+24V 0V
6
7
DI1
DI2
8
DI3
9
Digital Input
1
DO1
DO1
2
Digital Output
SINAMICS V10 Inverter
13
+10V
0V
Analog Input/Analog Output
14
15
AI1-
AI1+
AO1+
16
AO1-
17
18
N
220 AC Supply
L
DIP-switches
AO
(mA)
AO
(V)
I
U
AI
(mA)
AI
(V)
I
U
P6V5
M
RS-485
Com A Com B
Operator Panel
MOP-up Command
MOP-down Command
Lit while inverter running or alarm
Dim while inverter fault
Factory defaut setting:
Inverter running: Lamp ON
Inverter in any other status: Lamp OFF
Figure 6-10 Typical connection mode 10 (C10)
The DIP-switch settings in this application
DIP-switch (AO): Depends on the external signal source
DIP-switch (AI): Depends on the external signal source
Commissioning
6.1 Typical connection modes
SINAMICS V10
Operating Instructions, 08/2011, A5E03453178 (this is not an order number) 53