Par. No. Parameter name Range Unit Default
P0703 Function of digital input 3 0 - 99 - - 11
P1000 Selection of frequency setpoint 0 - 53 - - 2
P0725 PNP/NPN digital inputs 0 - 1 - - 1
* "xx" means current application macro.
Typical connection mode 10 (C10)
Description:
1. In LOC mode, motor start/stop, rotation direction and speed can be controlled via the 
operator panel.
2. In REM mode, motor start/stop can be controlled via an external signal source connected 
to DI1, motor MOP-up/MOP-down via external signal sources connected to DI2 and DI3, 
feedback value via an external sensor connected to terminals AI1+ and AI1-.
L1
L2
3 AC 400 V
L3
PE
Fuse
Contactor
Connection macro: C10
ON/OFF Command
RPM Meter
0 - 10 V DC or
0 - 20 mA DC
from Feedback Sensor
N
PE
L1
L3
L2
M
3~
U
V
W
5
+24V 0V
6
7
DI1
DI2
8
DI3
9
Digital Input
1
DO1
DO1
2
Digital Output
SINAMICS V10 Inverter
13
+10V
0V
Analog Input/Analog Output
14
15
AI1-
AI1+
AO1+
16
AO1-
17
18
N
220 AC Supply
L
DIP-switches
 AO 
(mA)
 AO 
 (V)
I
U
  AI 
(mA)
  AI
 (V)
I
U
P6V5
M
RS-485
Com A Com B
Operator Panel
MOP-up Command
MOP-down Command
Lit while inverter running or alarm
Dim while inverter fault
Factory defaut setting: 
Inverter running: Lamp ON
Inverter in any other status: Lamp OFF
Figure 6-10 Typical connection mode 10 (C10)
The DIP-switch settings in this application
DIP-switch (AO): Depends on the external signal source
DIP-switch (AI): Depends on the external signal source
Commissioning 
6.1 Typical connection modes
SINAMICS V10
Operating Instructions, 08/2011, A5E03453178 (this is not an order number) 53