Typical connection mode 6 (C06)
Description:
1. In LOC mode, motor start/stop, rotation direction and speed can be controlled via the
operator panel.
2. In REM mode, motor start/stop can be controlled via an external signal source connected
to DI1, motor set frequency via external signal sources connected to DI2 and DI3. When
DI2 is selected, you can change the motor set frequency with P1002 in the "Operation mode
⑤ - Access all the parameters (Page 71)" mode. When DI3 is selected, you can change
the motor set frequency with P1003 in the " Operation mode ⑤ - Access all the
parameters (Page 71) " mode. If both DI2 and DI3 are selected, the motor set frequency
is the sum of the value of P1002 and the value of P1003.
L1
L2
3 AC 400 V
L3
PE
Fuse
Contactor
Connection macro: C06
ON/OFF Command
Set Frequency 1
Set Frequency 1
RPM Meter
N
PE
L1
L3
L2
M
3~
U
V
W
5
+24V 0V
6
7
DI1
DI2
8
DI3
9
Digital Input
1
DO1
DO1
2
Digital Output
SINAMICS V10 Inverter
13
+10V
0V
Analog Input/Analog Output
14
15
AI1-
AI1+
AO1+
16
AO1-
17
18
N
220 AC Supply
L
DIP-switches
AO
(mA)
AO
(V)
I
U
AI
(mA)
AI
(V)
I
U
P6V5 M
RS-485
Com A Com B
Operator Panel
Dim while inverter fault
Factory defaut setting:
Lit while inverter running or alarm
Dim while inverter fault
Factory defaut setting:
Inverter running: Lamp ON
Inverter in any other status: Lamp OFF
Figure 6-6 Typical connection mode 6 (C06)
The DIP-switch settings
DIP-switch (AO): Depends on external RPM Meter
DIP-switch (AI): The DIP-switch setting in this application is inactive.
Commissioning
6.1 Typical connection modes
SINAMICS V10
48 Operating Instructions, 08/2011, A5E03453178 (this is not an order number)