Table 6-2 Select connection macro C02 with the operator panel after the wiring (please refer to
"Operation mode - Connection macro selection", and then below parameter settings
will be automatically finished.)
Par. No. Parameter name Range Unit Default
r0007 Selected connection macro and application macro C0100 - C1105 - - C02xx*
P0610 Motor I
2
t reaction 0 - 2 - - 2
P0701 Function of digital input 1 0 - 99 - - 13
P0702 Function of digital input 2 0 - 99 - - 14
P0703 Function of digital input 3 0 - 99 - - 1
P1000 Selection of frequency setpoint 0 - 53 - - 1
P0725 PNP/NPN digital inputs 0 - 1 - - 1
* "xx" means current application macro.
Typical connection mode 3 (C03)
Description:
1. In LOC mode, motor start/stop, rotation direction and speed can be controlled via the
operator panel.
2. In REM mode, motor start/stop can be controlled via an external signal source connected
to DI1, motor speed via an external potentiometer.
L1
L2
3 AC 400 V
L3
PE
Fuse
Contactor
Connection macro: C03
PE
L1
L3
L2
M
3~
U
V
W
ON/OFF Command
DC braking (optional)
5
+24V 0V
6
7
DI1
DI2
8
DI3
9
Digital Input
1
DO1
DO1
2
Digital Output
SINAMICS V10 Inverter
13
+10V
0V
RPM Meter
Speed Reference
Potentiometer
Analog Input/Analog Output
14
15
AI1-
AI1+
AO1+
16
AO1-
17
18
N
N
220 AC Supply
L
DIP-switches
AO
(mA)
AO
(V)
I
U
AI
(mA)
AI
(V)
I
U
P6V5 M
RS-485
Com A Com B
Operator Panel
Lit while inverter running or alarm
Dim while inverter fault
Factory defaut setting:
Inverter running: Lamp ON
Inverter in any other status: Lamp OFF
Figure 6-3 Typical connection mode 3 (C03)
The DIP-switch settings
Commissioning
6.1 Typical connection modes
SINAMICS V10
Operating Instructions, 08/2011, A5E03453178 (this is not an order number) 43