Par. No. Name Range Default Unit
P1210 Automatic restart 0 - 6 1 --
Configures automatic restart function
Possible Settings:
0 Disabled
1 Trip reset after power on
2 Restart after mains blackout
3 Restart after mains brown-/black-out or fault
4 Restart after mains brown-/black-out
5 Restart after mains blackout and fault
6 Restart after mains brown- /black-out or fault
Caution:
Use caution when setting P1210 ≥ 2. P1210 2 can cause the motor to restart automatically without toggling
the ON command.
Ever time when you change the operation mode to the "Motor data setting" mode, the setting of P1210 changes
by default to "1". To change the setting, go to the operation mode "Application macro selection" or "Access
all the parameters".
P1210 ON always active (permanently) On in no-voltage condition
Fault F0003 on All other faults on All faults on No faults on
Blackout Brownout Blackout Brownout Blackout Blackout
0 - - - - - -
1 Fault ack. - Fault ack. - Fault ack. -
2 Fault ack.
+ restart
- - - - Restart
3 Fault ack.
+ restart
Fault ack.
+ restart
Fault ack.
+ restart
Fault ack.
+ restart
Fault ack.
+ restart
-
4 Fault ack.
+ restart
Fault ack.
+ restart
- - - -
5 Fault ack.
+ restart
- Fault ack.
+ restart
- Fault ack.
+ restart
Restart
6 Fault ack.
+ restart
Fault ack.
+ restart
Fault ack.
+ restart
Fault ack.
+ restart
Fault ack.
+ restart
Restart
Note:
Flying start must be used in cases where the motor may still be turning (for example, after a short mains
break) or can be driven by the load (P1200).
If P1210 = 4, power brownout will cause the motor to restart, no matter whether the inverter is in LOC or REM
mode. In other cases, however, motor restart can only happen when the inverter is in REM mode.
Before the operator panel finishes the start course, the setpoint is 1.
P1215 Holding brake enable 0 - 1 0 --
Enables/disables holding brake function.
Possible settings:
0 Motor holding brake disabled
1 Motor holding brake enabled
Parameter list
SINAMICS V10
98 Operating Instructions, 08/2011, A5E03453178 (this is not an order number)