Par. No. Parameter name Range Unit Default
P1000 Selection of frequency setpoint 0 - 53 - - 5
P0725 PNP/NPN digital inputs 0 - 1 - - 1
* "xx" means current application macro.
Typical connection mode 2 (C02)
Description:
1. In LOC mode, motor start/stop, rotation direction and speed can be controlled via the
operator panel.
2. In REM mode, motor start/stop can be controlled via an external signal source connected
to DI3, MOP-up (for increasing motor frequency)/MOP-down (for decreasing motor
frequency) via external signal sources connected to DI1 and DI2.
L1
L2
3 AC 400 V
L3
PE
Fuse
Contactor
Connection macro: C02
PE
L1
L3
L2
M
3~
U
V
W
MOP-up Command
MOP-down Command
ON/OFF Command
5
+24V
0V
6
7
DI1
DI2
8
DI3
9
Digital Input
1
DO1 DO1
2
Digital Output
SINAMICS V10 Inverter
13
+10V
0V
Analog Input/Analog Output
14
15
AI1-
AI1+
AO1+
16
AO1-
17
18
RPM Meter
N
N
220 AC Supply
L
DIP-switches
AO
(mA)
AO
(V)
I
U
AI
(mA)
AI
(V)
I
U
P6V5 M
RS-485
Com A Com B
Operator Panel
Lit while inverter running or alarm
Dim while inverter fault
Factory defaut setting:
Inverter running: Lamp ON
Inverter in any other status: Lamp OFF
Figure 6-2 Typical connection mode 2 (C02)
The DIP-switch settings
DIP-switch (AO): Depends on external RPM Meter
DIP-switch (AI): The setting in this application is inactive
Commissioning
6.1 Typical connection modes
SINAMICS V10
42 Operating Instructions, 08/2011, A5E03453178 (this is not an order number)