Par. No. Name Range  Default Unit
P2000 Reference frequency 1.00 - 300.00 50.00 Hz
Parameter P2000 represents the reference frequency for frequency values which are displayed / transferred 
as a percentage or a hexadecimal value. Where:
- hexadecimal 4000 H ⇒P2000 
- percentage 100 % ⇒ P2000 (e.g.: ADC)
r2036 CtrlWrd1 from operator panel -- -- --
Displays control word 1 from operator panel (i.e. word 1).
Bitfields:
Bit00 ON/OFF1 0 NO 1 YES
Bit01 OFF2: Electrical stop 0 YES 1 NO
Bit02 OFF3: Fast stop 0 YES 1 NO
Bit03 Pulses enabled 0 NO 1 YES
Bit04 RFG enable 0 NO 1 YES
Bit05 RFG start 0 NO 1 YES
Bit06 Setpoint enable 0 NO 1 YES
Bit07 Fault acknowledge 0 NO 1 YES
Bit08 JOG right 0 NO 1 YES
Bit09 JOG left 0 NO 1 YES
Bit10 Control from the operator panel 0 NO 1 YES
Bit11 Reverse (setpoint inversion) 0 NO 1 YES
Bit13 Motor potentiometer MOP up 0 NO 1 YES
Bit14 Motor potentiometer MOP down 0 NO 1 YES
Bit15 Local / Remote 0 NO 1 YES
Note:
The 7-segment display of the bit-parameters (binary parameters) is explained in Fig. 6-12 of Section 6.3.2.
r2110 [4] Warning number -- -- --
Displays warning information.
A maximum of 2 active warnings (indices 0 and 1) and 2 historical warning (indices 2 & 3) may be viewed.
Index:
r2110[0]: Recent warnings - -, warning 1
r2110[1]: Recent warnings - -, warning 2
r2110[2]: Recent warnings - 1, warning 3
r2110[3]: Recent warnings - 1, warning 4
Parameter list
SINAMICS V10
102 Operating Instructions, 08/2011, A5E03453178 (this is not an order number)