Typical connection mode 1 (C01) - Out-of-box application 
Description: 
1. Only input power and motor 3-phase connection
2. Motor start/stop, rotation direction and speed are controlled via the operator panel only.
L1
L2
3 AC 400 V
L3
PE
PE
L1
L3
Fuse
Contactor
L2
M
3~
U
V
W
5
+24V 0V
6
7
DI1
DI2
8
DI3
9
Digital Input
1
DO1 DO1
2
Digital Output
SINAMICS V10 Inverter
Connection macro: C01
RS-485
N
220 AC Supply
Lit while inverter running or alarm
Dim while inverter fault
L
13
+10V
0V
RPM Meter
(Operation from the inverter operator panel only)
Analog Input/Analog Output
14
15
AI1-
AI1+
AO1+
16
AO1-
17
18
N
DIP-switches
 AO 
(mA)
 AO 
 (V)
I
U
 AI 
(mA)
 AI
 (V)
I
U
L1
L2
L3
PE
PE
L1
L3
Fuse
Contactor
L2
M
3~
U
V
W
5
+24V 0V
6
7
DI1
DI2
8
DI3
9
Digital Input
1
DO1 DO1
2
Digital Output
N
220 AC Supply
Factory defaut setting: 
Inverter running: Lamp ON
Inverter in any other status: Lamp OFF
L
13
+10V
0V
RPM Meter
(Operation from the inverter operator panel only)
Analog Input/Analog Output
14
15
AI1-
AI1+
AO1+
16
AO1-
17
18
N
DIP-switches
 AO 
(mA)
 AO 
 (V)
I
U
 AI 
(mA)
 AI
 (V)
I
U
P6V5 M
RS-485
Com A Com B
Operator Panel
Figure 6-1 Typical connection mode 1 (C01)
The DIP-switch settings 
DIP-switch (AO): Depends on external RPM Meter
DIP-switch (AI): The setting in this application is inactive
Table 6-1 Select connection macro C01 with the operator panel after the wiring (please refer to 
"Operation mode ② - Connection macro selection", and then below parameter settings 
will be automatically finished.)
Par. No. Parameter name Range Unit Default
r0007 Selected connection macro and application macro C0100 - C1105 - - C01xx*
P0610 Motor I
2
t reaction 0 - 2 - -  1
P0701 Function of digital input 1 0 - 99 - -  0
P0702 Function of digital input 2 0 - 99 - - 0
P0703 Function of digital input 3 0 - 99 - - 0
Commissioning 
6.1 Typical connection modes
SINAMICS V10
Operating Instructions, 08/2011, A5E03453178 (this is not an order number) 41