Figure 6-27 Viewing a normal read-only parameter (example)
 
 
Note
The procedure to set an indexed editable parameter (Pxxxx[x]) is the same as shown in this 
example. 
The alternatives to change parameter values are the same as afore-described under Fig. 6-8, 
but one exception is: if the value range available for setting consists of discontinuous values 
(for example, for P0005), when you turn OK to appear a value that is not available for this 
parameter and then press OK, an error indication ("Err- -") will appear indicating value setting 
is impossible. Then, the display will automatically jump to the next immediately followed and 
available-for-setting value. 
 
Button/keys inactive in this mode
If the current connection macro selected is "C01xx" or "C05xx", the LOC/REM key is inactive 
in this mode.
The STOP and RUN keys are active when one of the preconfigured connection modes is 
selected and currently the command source is from the operator panel.
The OK button and the SET key are always active in this mode. 
Long-pressed STOP key is always active.
6.7 Factory reset
 
Factory reset (P0970)  
Proceed the following steps to perform a factory reset:
1. Stop the motor operation.
2. Go to the "Access all the parameters" mode, set P0970 to desired value (please refer to 
below table).
Commissioning 
6.7 Factory reset