Table 6-10 Select connection macro C10 with the operator panel after the wiring (please refer to
"Operation mode - Connection macro selection", and then below parameter settings
will be automatically finished.)
Par. No. Parameter name Range Unit Default
r0007 Selected connection macro and application macro C0100 - C1105 - - C10xx*
P0610 Motor I
2
t reaction 0 - 2 - - 2
P0701 Function of digital input 1 0 - 99 - - 1
P0702 Function of digital input 2 0 - 99 - - 13
P0703 Function of digital input 3 0 - 99 - - 14
P1000 Selection of frequency setpoint 0 - 53 - - 1
P0725 PNP/NPN digital inputs 0 - 1 - - 1
* "xx" means current application macro.
NOTICE
The PI controller function is valid only in this connection mode and when the current control
mode is set to REM mode.
In this connection mode, PI setpoint must be set via P2240 and feedback value shall,
depending on actually connected sensor, be scaled via P0753 to P0761.
Besides parameters listed in Auto hotspot , P2280 (default value: 0.500), P2285 (default
value: 10.000s) and P2293 (default value: 10.00s) are also related to connection mode.
Commissioning
6.1 Typical connection modes
SINAMICS V10
54 Operating Instructions, 08/2011, A5E03453178 (this is not an order number)