Setting Meaning
Forced checking procedure of the switch-off
signal paths
p9659
Sets the time interval for performing the forced checking procedure and
testing the safety switch-off signal paths. Within the parameterized time,
STO must have been deselected at least once. The monitoring time is reset
at every STO deselection.
Commissioning and configuring
6.6 Configuring safety functions integrated in the drive
Safety Integrated (with SINAMICS S120)
Commissioning Manual, 02/2020, A5E46305916B AB 271