Page #182 background imageLoading...
Page #182 background image
(1) Push the holder, push the sealing cap to the back and remove it
(2) Unlock the eject lever
(3) Remove the SDHC memory card
²
Unpack the new SDHC memory card.
Do not touch the contacts of the SDHC memory card with your fingers.
²
Insert the new SDHC memory card.
When inserting, make sure that the SDHC memory card is properly aligned: The side with the contacts
must be facing up, the side with the sticker facing down.
[dw_insert_SDHC, 1, --_--]
Figure 5-21 Inserting the SDHC Memory Card into the Device
!
CAUTION
Exercise caution when removing the SDHC memory card from a defective device.
If you want to remove the SDHC memory card from a defective device and to insert the card into another
healthy device and if the data must be kept, note the following:
Noncompliance with the specified measures can result in loss of data.
²
To avoid a reformatting of the SDHC memory card, you must first import the parameters of the defec-
tive device to another device.
²
You can insert the SDHC memory card in the other device and use it only then.
²
The recordings on the SDHC memory card from the defective device can still be read in the other
device.
²
Insert the sealing cap back again.
²
Resume operation of the device.
Working on the Device
5.6 SDHC Memory Card
182 SIPROTEC 5, Hardware Description, Manual
C53000-G5040-C002-C, Edition 10.2017

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 5 Series and is the answer not in the manual?

Siemens SIPROTEC 5 Series Specifications

General IconGeneral
Protection FunctionsOvercurrent, differential, distance, over/under voltage, frequency
Communication ProtocolsIEC 61850, IEC 60870-5-103, Modbus, DNP3, PROFINET
DisplayGraphical LCD with touch functionality
Inputs/OutputsDigital and analog inputs/outputs, configurable
Power Supply24-250V DC or 100-240V AC
MountingPanel or rack mounting
Environmental ConditionsOperating temperature: -25°C to +70°C, humidity up to 95% non-condensing
Product TypeMultifunctional protection relay
ApplicationPower generation, transmission, distribution, industrial plants
CybersecurityIEC 62351, role-based access control, secure communication
Modular DesignYes, with plug-in modules for flexibility
HardwareRobust design with high processing power
SoftwareSIPROTEC 5 DIGSI software for configuration and operation
Control FunctionsRemote control, switching sequences, interlocking
Monitoring FunctionsEvent recording, disturbance recording, measurement values
HMIIntegrated HMI with graphical display and pushbuttons. Remote HMI via web browser or dedicated software. User-configurable dashboards and single-line diagrams.
Time SynchronizationIRIG-B, SNTP, PTP (IEEE 1588)
CertificationsIEC, IEEE, UL, CE