153
3465 2.AR:DeadT.2Flt 0.01 .. 1800.00 sec; 1.20 sec Dead time after 2phase faults
3466 2.AR:DeadT.3Flt 0.01 .. 1800.00 sec; 0.50 sec Dead time after 3phase faults
3468 2.AR:Dead 3Trip 0.01 .. 1800.00 sec; 0.50 sec Dead time after 3pole trip
3469 2.AR:DeadT.EV. 0.01 .. 1800.00 sec 1.20 sec Dead time after evolving fault
3470 2.AR:52? CLOSE YES