Functions
2.4 Backup Overcurrent
SIPROTEC, 7SD80, Manual
E50417-G1140-C474-A1, Release date 09.2011
96
2.4.6 Information List
2644 51(N)-B PilotBI NO
YES
NO Instantaneous trip via Pilot
Prot./BI
2644 67(N)TOC Pil/BI NO
YES
NO Instantaneous trip via Pilot
Prot./BI
2650 50(N)-STUB OpMo ON
Only Emer. prot
OFF
OFF 50(N)-STUB Operating
Mode
2651 50-STUB PICKUP 1A 0.10 .. 25.00 A; ∞ 1.50 A 50-STUB Pickup
5A 0.50 .. 125.00 A; ∞ 7.50 A
2652 50-STUB DELAY 0.00 .. 30.00 sec; ∞ 0.30 sec 50-STUB Delay
2653 50-STUB Inrush NO
YES
NO 50-STUB Inrush blocking
2654 50N-STUB PICKUP 1A 0.05 .. 25.00 A; ∞ 0.20 A 50N-STUB Pickup
5A 0.25 .. 125.00 A; ∞ 1.00 A
2655 50N-STUB DELAY 0.00 .. 30.00 sec; ∞ 2.00 sec 50N-STUB Delay
2656 50STUB Pilot/BI NO
YES
NO Instantaneous trip via Pilot
Prot./BI
No. Information Type of In-
formation
Comments
7104 >BLOCK 50-B1 SP >BLOCK 50-B1 Backup OverCurrent
7105 >BLOCK 50-B2 SP >BLOCK 50-B2 Backup OverCurrent
7106 >BLOCK 51-B SP >BLOCK 51-B Backup OverCurrent
7107 >BLOCK 50N-B1 SP >BLOCK 50N-B1 Backup OverCurrent
7108 >BLOCK 50N-B2 SP >BLOCK 50N-B2 Backup OverCurrent
7109 >BLOCK 51N SP >BLOCK 51N Backup OverCurrent
7110 >5X-B InstTRIP SP >50(N)/51(N) BackupO/C InstantaneousTrip
7112 >BLOCK 67-TOC SP >BLOCK Backup OverCurrent 67-TOC
7114 >BLOCK 67N-TOC SP >BLOCK Backup OverCurrent 67N-TOC
7115 >BLOCK 67-B1 SP >BLOCK Backup OverCurrent 67-B1
7116 >BLOCK 67N-B1 SP >BLOCK Backup OverCurrent 67N-B1
7117 >BLOCK 67-B2 SP >BLOCK Backup OverCurrent 67-B2
7118 >BLOCK 67N-B2 SP >BLOCK Backup OverCurrent 67N-B2
7130 >BLOCK 50-STUB SP >BLOCK 50-STUB
7132 >BLOCK 50N-STUB SP >BLOCK 50N-STUB
7152 5X-B BLOCK OUT 50(N)/51(N) Backup O/C is BLOCKED
7153 5X-B ACTIVE OUT 50(N)/51(N) Backup O/C is ACTIVE
7154 50(N)-B2 OFF OUT Backup O/C stage 50(N)-B2 is sw. OFF
7155 50(N)-B1 OFF OUT Backup O/C stage 50(N)-B1 is sw. OFF
7156 50(N)-STUB OFF OUT Backup O/C stage 50(N)-STUB is sw. OFF
7157 51(N)-B OFF OUT Backup O/C stage 51(N)-B is sw. OFF
7161 5X-B PICKUP OUT 50(N)/51(N) Backup O/C PICKED UP
Addr. Parameter C Setting Options Default Setting Comments

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SD80 and is the answer not in the manual?

Siemens SIPROTEC 7SD80 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7SD80
CategoryProtection Device
LanguageEnglish

Related product manuals