A.4 Current Transformer Requirements
A.4.1 Current Transformer Ratio: 
A.4.2 Overcurrent Factors 
Maximum ratio between primary currents of the 
current transformers at both ends of the protect-
ed object. 
0.25 ≥ I
pn-local
 / I
pn-remote
 ≤ 4 
Note: 
The maximum ratio can also be selected greater 
or smaller. It may be that the sensitivity of the dif-
ferential protection indicated in the technical 
data are no longer observed. 
I
pn-local
: Primary rated transformer current of the local device 
I
pn-remote
: Primary rated transformer current of the remote 
device 
Required minimum effective accuracy limiting 
factor 
and K’
SSC min
 = 30
K'
SSC
 Effective symmetrical short-circuit current factor 
K
SSC
: Specified symmetrical short-circuit current factor 
(example: Current transformer 5P20: K
SSC
 = 20) 
I
SSC -max(ext. fault)
: maximum through-flowing 
short-circuit current
I
pn
: Primary transformer rated current 
R
CT
: Secondary direct current winding resistance of the 
current transformer at 75 °C 
R
b
: Rated burden resistance of the current transformer 
R’
b
: Connected burden resistance at the current transformer 
(usually resistance of the current transformer feed cable + 
burden resistance of the protection device) 
Example: 
Current transformer: 5P40, 5 VA 
I
sn
 = 1 A 
I
pn
 = 500 A 
R
b
 = 5 Ω = 5 VA / I
sn
2
 
R
CT
 = 3 Ω 
R’
b
 : 0.6 Ω 
I
SSC-max(ext. fault)
: 20 kA
88.9 > 48 and 88.9 > 30 
transformer OK! 
I
sn
: Secondary transformer rated current